25
38
Solar energy feed to grid
configuration
Solar energy feed to grid
disable (default)
Solar energy feed to grid
enable.
41
Maximum battery
discharging current
Disable (Default)
If selected, battery discharge
protection is disabled.
30A
The setting range is from 30 A
to 150 A. Increment of each
click is 10A.
If discharging current is higher
than setting value, battery will
stop discharging. At this time,
if the utility is available, the
inverter will operate in bypass
mode. If no utility is available,
the inverter will shut down
output for 5 minutes.
150A
83
Erase all data log
Not reset (Default)
Reset
84
Data log recorded interval
*The maximum data log
number is 1440. If its over
1440, it will re-write the
first log.
3 minutes
5 minutes
10 minutes (default)
20 minutes