1.1 General technical parameters
Item Basis Condition
Climate environment
Humidity
Cold: IEC68-2-1
Heat: IEC68-2-2
Horizontal installation
Vertical installation
-20 ~ 70 C
-20 ~ 70 C
Storage/transportation -40 C ~ +70 C
Relative humidity IEC68-2-30 5% ~ 95% without condensation
Pollutants
SO
2
10cm
3
/m
3
, 4days
Mechanical environment
Protection type IP20
Vibration 2
IEC68-2
Impact IEC68-2-27
18 impacts(semi sine 15g/11mins)
Fall IEC68-2-31 Falling height 50mm
Freely falling objects (with package)
IEC68-2-32 1m
Electromagnetic compatibility (EMC)
Static discharge Severe grade 3
8KV air discharge,
6KV contact discharge
Electromagnetic eld IEC801-3 Field strength 10V/m
Interference suppression EN55011 Limitation grade B group 1
Shock pulse
2.2KV for power line
2.2KV for signal line
IEC/VDE safety information
Insulation Intensity IEC1131
Meet the requirements
10~57Hz(constant amplitude 0.15mm)
57~150Hz(constant acceleration 2g)
Atmospheric pressure
795 ~ 1080kpa
IEC68-2-43
IEC68-2-42
H
2
S 1cm
3
/m
3
, 4days
IEC801-4
severe grade 3