EasyManua.ls Logo

Assa Abloy EffEff 1338-14 - Mounting; Regulations for positioning; Preparatory tasks for installation

Assa Abloy EffEff 1338-14
68 pages
Go to English
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
42
EN
Mounting
Regulations
In accordance with “Guidelines for electronic locking systems in escape route
doors,” the terminal must be positioned in such a way that the emergency
push-button is placed between 850 mm and 1200 mm above the upper edge of
the finished floor. A height of 850 mm above the upper edge of the finished floor
is recommended. Further regulatory requirements can be found in respective
local building ordinances.
Preparatory tasks
The escape door control terminal must be installed in the immediate vicinity of
the escape door. It is intended for surface-mounted wall mounting to meet
structural requirements.
6
Fig. 2 :
Preparatory tasks
2
3
3
1
Mains supply line
e. g.: NYM-J
Control lines
e.g.: J-Y (ST)Y
1.5 mm²
to
2.5 mm²
I
Traction relief
I
Loosely attach
additional fastening
with cable ties
I
For flexlines:
use wire end-sleeves
1
Mounting

Table of Contents

Related product manuals