Refresh cycle
(Thermostat profile
details dialog, Misc tab)
The Orion EMS system can in
setback control run the A/C unit
every 25 minutes for a period of
2 minutes to re-circulate the air
in the room; this optional function
is only for cooling mode.
Room not occupied
timer
(Thermostat profile
details dialog,
Timeout tab)
This is the amount of time the
thermostat maintains the guest
setting after the room has entered
the unoccupied state.
Room not sold timer
(Thermostat profile
details dialog,
Timeout tab)
When the room has been
unoccupied for this number
of hours, it will enter unsold mode.
Set door state
to closed when
ajar alarm received
(Thermostat profile
details dialog, Misc tab)
If the checkbox Set door state
to closed when door ajar alarm
received is marked, the door state
is set to closed once the door
ajar timeout has been triggered.
This allows the thermostat to go
to occupied state even if the door
is not physically closed.
Note: This checkbox is applicable
if you have a malfunctioning
door switch.
Temperature display
(Thermostat profile
details dialog, Misc tab)
The thermostat will show either
the room temperature or the
temperature that has been set
by the guest.
Room temperature/
set temperature
Thermostat deadband
(Thermostat profile
details dialog,
Deadband tab)
The range the temperature is
allowed to drift from the setpoint
before the heat or air conditioner
is turned on
Unoccupied setbacks
(Thermostat profile
details dialog, Limits tab)
The applicable number of degrees
as upper limit and lower limit for
setback if a room is unoccupied.
Static/dynamic
Static upper
(72-90 ºF)
Static lower
(55-70 ºF)
Dynamic upper
(2-8 ºF offset)
Dynamic lower
(2-8 ºF offset)
Static:
78 ºF
68 ºF
Dynamic:
4 ºF
4 ºF
Unsold setback
(Thermostat profile
details dialog, Limits tab)
The applicable number of degrees
as upper limit and lower limit for
setback if a room is unsold.
Summer
(74-90 ºF)
Winter
(55-70 ºF)
Welcome scene
(Thermostat profile
details dialog, Misc tab)
If desired, it is possible to have a
welcome scene which it is activated
when the occupancy state for a
room changes from unsold to
unoccupied.
Disabled
Use RV output
Use G2 output
Use solid state
relay