This function code is used to select the
electromotion and braking torque upper-limit
setting source selection.
0: Keypad setting upper-limit frequency
(P03.20 sets P03.18 and P03.21 sets P03.19)
1: Analog AI1 setting upper-limit torque
2: Analog AI2 setting upper-limit torque
3: Analog AI3 setting upper-limit torque
4: Pulse frequency HDI setting upper-limit
torque
5: MODBUS communication setting upper-limit
torque
6~8: Reserved
Note: Setting mode 1~8,100% corresponds to
three times of the motor current.
The usage of motor in weakening control.
Function code P03.22 and P03.23 are effective
at constant power. The motor will enter into
the weakening state when the motor runs at
rated speed. Change the weakening curve by
modifying the weakening control coefficient.
The bigger the weakening control coefficient is,