45
Detailed instruction of parameters
2:AI2 setting voltage
3:AI3 setting voltage
4:HDI setting voltage
5:Multi-step speed setting voltage;
6:PID setting voltage;
7:MODBUS communication setting voltage;
8~10: Reversed
Note: 100% corresponds to the rated voltage
of the motor.
The function code is the voltage digital set
value when the voltage setting channel is
selected as “keypad selection”
The setting range:0.0%~100.0%
Voltage increasing time is the time when the
inverter accelerates from the output minimum
voltage to the output maximum voltage.
Voltage decreasing time is the time when the
inverter decelerates from the output maximum
voltage to the output minimum voltage.
The setting range:0.0~3600.0s
Set the upper and low limit of the output
voltage.
The setting range of P04.31:P04.32~100.0%
(the rated voltage of the motor)
The setting range of P04.32:0.0%~ P04.31
(the rated voltage of the motor)
Weakenin
g
coefficient
in
constant
power
zone
Adjust the output voltage of the inverter in
SVPWM mode when weakening.
Note: Invalid in the constant torque mode.
The setting range of P04.33:1.00~1.30
P05 Group Input terminals
0: HDI is high pulse input. See P05.49~P05.54
1:HDI is switch input