Line Function Setting range
or display
Setting
increment
Basic
setting
850 I Floor curing function (gure 1) Off
- Off: Early interruption of the current programme, programme inactive.
- Operational heating.
- Heating ready for occupation.
- Operational heating + ready heating.
- Ready heating + operational heating.
- Manual: Manual mode enables you to programme your own concrete slab drying time.The function ends
automatically after 25 days.
" Please comply with the
standards and instructions
of the manufacturer of
the building ! A good
performance of this function
is only possible with an
installation correctly
implemented (hydraulic,
electricity and adjustments) !
This function can be stopped
by anticipation when setting
the adjustment to "Off".
50
45
40
35
30
20
50
25
55
1157
X
10
18
25
15
1
gure 1 - Diagram of the concrete slab drying programmes
Heating ow temperature °C
Operational heating + Heating ready for occupation
Heating ready for occupation
Day
Operational
heating
851 I Floor curing setpoint manually
(if line 850 = manual)
0... 95 °C 1 °C 25 °C
This function enables you to set the custom concrete slab drying temperature. This temperature remains xed.
The concrete slab-drying programme stops automatically after running for 25 days.
856 I Floor curing day current 0... 32
857 I Floor curing day completed 0... 32
900 S Operating mode changeover None, Protection mode,
Reduced, Comfort, Automatic
1 Reduced
Operating mode at end of concrete slab drying period
Cooling circuit 1
If the installation is tted with the cooling kit (Only with the cooling kit option).
901 U Operating mode Protection, Automatic, Reduced,
Comfort
Protection
902 U Comfort cooling setpoint 17... 40 °C 0,5 °C 24 °C
903 U Reduced setpoint 5... 40°C 26 °C
908 I Flow temp setp at OT° 25°C 6... 35 °C 0,5 °C 20 °C
909 I Flow temp setp at OT° 35°C 6... 35 °C 0,5 °C 16 °C
912 I Cooling limit at OT° 8... 35 °C 0,5 °C 24 °C
913 S Lock time at end of heating / cooling 8... 100 1 h 24 h
918 S Summer comp start at OT° 20... 50 °C 1 °C 26 °C
919 S Summer comp end at OT° 20... 50 °C 1 °C 40 °C
920 S Summer comp setp increase 1... 10 °C 1 °C 4 °C
923 S Flow temp setp min OT° 25°C 6... 35 °C 0,5 °C 18 °C
924 S Flow temp setp min OT° 35°C 6... 35 °C 0,5 °C 18 °C
Installation and operation manual "1734 - EN"
Heat pump air/water split 1 service alféa extensa +
- 54 -