Compressor
type
Supply
voltage (V)
Overload relay
(A)
Fuses Class gL/
gG (Type 2) (A)
2X3 fuses
2X3 cables to
contactor
Fuses Class gL/
gG (Type 2) (A)
3 fuses
2X3 cables to
contactor
Fuses Class gL/
gG (Type 2) (A)
3 fuses
3 cables to
contactor
(bridges to be
installed by
customer)
GA 250 400 289 2x (3x355) -- --
GA 250 500 234 2x (3x300) -- --
60Hz IEC compressors with ABB motors
GA 90 up to GA 315 and GR 110 up to GR 200
Compressor
type
Supply
voltage (V)
Overload relay
(A)
Fuses Class gL/
gG (Type 2) (A)
2X3 fuses
2X3 cables to
contactor
Fuses Class gL/
gG (Type 1) (A)
3 fuses
2X3 cables to
contactor
Fuses Class gL/
gG (Type 1) (A)
3 fuses
3 cables to
contactor
(bridges to be
installed by
customer)
GA 90 220-230 208 2x (3x300) -- --
GA 90 380 122 2x (3x160) 3x250 --
GA 90 440-460 104 2x (3x160) -- 3x224
GA/GR 110 220-230 257 2x (3x355) -- --
GA/GR 110 380 149 2x (3x200) 3x300 --
GA/GR 110 440-460 129 2x (3x160) 3x300 --
GA/GR 160 380 195 2x (3x250) 3x400 --
GA/GR 160 440-460 169 2x (3x224) -- --
GA/GR 200 380 242 2x (3x355) -- --
GA/GR 200 440-460 204 2x (3x300) -- --
GA 250 380 284 2x (3x400) -- --
GA 250 440-460 246 2x (3x315) -- --
GA 315 380 319 2x (3x400) -- --
GA 315 440-460 278 2x (3x355) -- --
60 Hz CSA/UL compressors with Siemens or Weg motor
GA 90 up to GA 315 and GR 110 up to GR 200
Instruction book