- 28 -
Qc2002™ Menu Overview
At Qc2002™, the LCD will show following
information:
–in Normal condition (scroll through the
information using UP and DOWN):
• Status (eg: preheat, crank, cooldown, extended
stop time, …) (pop-up: this display is only
shown when a Special status comes up)
• Line voltages of the generator
• Controller type & version
• Parameter list
•Alarm list
• LOG list
• Service Timer 1 & Service Timer 2
• Battery Voltage
• RPM (speed)
• Coolant temperature
• Oil pressure
• Fuel level
• kWh counter
• Power factor, the frequency of the generator
and the frequency of the mains 
• Line voltage, frequency and active power of
the generator
• Active, reactive and apparent power of the
generator
• Generator currents
• Phase voltages of the mains
• Line voltages of the mains
• Phase voltages of the generator
–in Alarm condition (scroll through the
information using UP and DOWN):
• a list of all active Alarms
It's possible to scroll through the views, using the UP
and DOWN buttons. The scrolling is continuous. 
If a Special status comes up, the Status Display is
shown. 
If an Alarm comes up, the Alarm Display is shown.
Line voltages generator display
This view shows the line voltages of the generator.
Controller type and version display
This view shows the controller type and the ASW
version number.
Mains 
contactor
Green LED indicates that it is 
possible to close the Mains 
Contactor (only in AMF mode), if 
the Generator contactor is open.
Alarm Flashing red LED indicates that an 
alarm is present. A continuous red 
LED indicates that the alarm has 
been acknowledged by the user. The 
exact alarm is shown on the display.
G L1-L2
G L2-L3
G L3-L1
400V
400V
400V
Qc2002 CAN
1.00.1