Installations with more generators
(**) The power management system (PMS) allows communication between the Qc4002™ modules over CAN-bus. It has a fully intelligent system, which will start/load/
stop the generator according to the actual load and to the status of each generator. The installation can contain up to 16 Qc4002™ modules. If the Mains is included in the
installation, then an extra Qc4002™ module is required. The installation can be monitored and controlled via the PMS Software Package. For details on this application,
please contact Atlas Copco.
Application type Mode Comments
Island operation
SEMI-AUTO mode = Manual paralleling between generators
AUTO mode = Remote paralleling between generators
AMF operation
(SEMI-AUTO mode) AMF operation will not function properly !
AUTO mode PMS + Qc4002™ Mains module (**)
Peak shaving
SEMI-AUTO mode PMS + Qc4002™ Mains module (**)
AUTO mode PMS + Qc4002™ Mains module (**)
Fixed Power
SEMI-AUTO mode PMS + Qc4002™ Mains module (**)
AUTO mode PMS + Qc4002™ Mains module (**)
Load Take Over
SEMI-AUTO mode PMS + Qc4002™ Mains module (**)
AUTO mode PMS + Qc4002™ Mains module (**)
Main Power Export
SEMI-AUTO mode PMS + Qc4002™ Mains module (**)
AUTO mode PMS + Qc4002™ Mains module (**)
Power Management System
(SEMI-AUTO mode) PMS + Qc4002™ Mains module (**)
AUTO mode PMS + Qc4002™ Mains module (**)