- 50 -
Control setup
Synchronisation
2001 Type
Static sync. – Dynamic Sync.
2000 Sync. type
2141 Delay
30.0 s – 300.0 s
2142 Output A
Not Used – Option dependent
2143 Output B
Not Used – Option dependent
2144 Enable
Off – On
2145 Failclass
Alarm (1) – Trip MB (6)
2151 Output A
Not Used – Option dependent
2152 Output B
Not Used – Option dependent
2153 Failclass
Alarm (1) – Trip MB (6)
2140 MB sync failure
2150 Phase seq error
2121 Setpoint
2.0% – 20.0%
2122 Delay
0.1 s – 2.0 s
2123 Output A
Not Used – Option dependent
2124 Output B
Not Used – Option dependent
2125 Enable
Off – On
2131 Delay
30.0 s – 300.0 s
2132 Output A
Not Used – Option dependent
2133 Output B
Not Used – Option dependent
2134 Enable
Off – On
2135 Failclass
Alarm (1) – Trip MB (6)
2120 Sync. window
2130 GB sync failure
2261 Break
Close GB – Close GB+TB
2262 Delay
0.0 s – 999.0 s
2263 Rpm OK
0 rpm – 4000 rpm
2271 Delay
0.0 s – 999.0 s
2272 Output A
Not Used – Option dependent
2273 Output B
Not Used – Option dependent
2274 Enable
Off – On
2275 Failclass
Alarm (1) – Trip MB (6)
2241 GB
Not Used – Option dependent
2242 MB
Not Used – Option dependent
2251 Setpoint
0 rpm – 4000 rpm
2252 Delay
0.0 s – 999.0 s
2253 Output A
Not Used – Option dependent
2254 Enable
Off – On
2240 Sep. sync. relay
2250 Close bef. exc.
2260 Breaker seq.
2270 Cl.bef.exc.fail