- 75 -
Stopping Qc1002™
To stop the unit locally, proceed as
follows:
– Switch off the load.
– Switch off circuit breaker Q1.
– Let the engine run for about 5 minutes.
– Stop the engine by using the STOP button on the
Qc1002™ module.
– Put the starter switch S20 in position O (OFF) to
shut down the voltage apply towards the
Qc1002™ module.
– Lock the side doors and the door of the indicators
and control panel to avoid unauthorized access.
To stop the unit when the starter
switch is in position , proceed as
follows:
– Switch off the load.
– Stop the engine by putting the remote start/stop
switch in position stop or by using the STOP
button on the Qc1002™ module. When the unit is
stopped with the STOP button in Remote Mode, it
will automatically go to Manual Mode.
– Put the starter switch S20 in position O (OFF) to
shut down the voltage apply towards the
Qc1002™ module.
– Lock the side doors and the door of the indicators
and control panel to avoid unauthorized access.
Operating Qc2002™
Starting Qc2002™
To start up the unit locally, proceed
as follows:
– Switch on the battery switch.
– Switch off circuit breaker Q1. This is not
necessary when a plant contactor is installed
between Q1 and the load.
– Put the starter switch S20 in position I (ON).
Voltage is applied to the Qc2002™ module.
– The unit can be started manually by pressing the
START button on the Qc2002™ module.
– The unit will start. The starting attempt will take
maximum 12 seconds.
– Switch on circuit breaker Q1 in case no contactor
is installed.
To start up the unit from a remote
location, proceed as follows:
– Put the starter switch S20 in position I (ON).
Voltage is applied to the Qc2002™ module.
– Switch on circuit breaker Q1.
The generator’s doors may only
remain opened for short periods
during operation, to carry out
checks for example.