- 54 -
Output setup
4241 Output A
Not Used – Option dependent
4242 Output B
Not Used – Option dependent
4243 Enable
Off – On
4244 Failclass
Alarm (1) – Trip MB (6)
4371 Output A
Not Used – Option dependent
4372 Output B
Not Used – Option dependent
4373 Enable
Off – On
4374 Failclass
Alarm (1) – Trip MB (6)
4501 Output A
Not Used – Option dependent
4502 Output B
Not Used – Option dependent
4503 Enable
Off – On
4504 Failclass
Alarm (1) – Trip MB (6)
4521 Setpoint
100.0% – 150.0%
4522 Delay
0.1 s – 100.0 s
4523 Output A
Not Used – Option dependent
4524 Output B
Not Used – Option dependent
4525 Enable
Off – On
4526 Failclass
Alarm (1) – Trip MB (6)
4541 Delay
0.0 s – 20.0 s
4542 Output A
Not Used – Option dependent
4543 Output B
Not Used – Option dependent
4544
Enable
Off – On
4545 Failclass
Alarm (1) – Trip MB (6)
4551 Output A
Not Used – Option dependent
4552 Output B
Not Used – Option dependent
4553 Enable
Off – On
4554 Failclass
Alarm (1) – Trip MB (6)
4971 Setpoint
12.0 V – 36.0 V
4972 Delay
0.0 s – 999.0 s
4973 Output A
Not Used – Option dependent
4974 Output B
Not Used – Option dependent
4975 Enable
Off – On
4976 Failclass
Alarm (1) – Trip MB (6)
4981
4982
4983
4984
4985
4986
Setpoint
8.0 V – 32.0 V
Delay
0.0 s – 999.0 s
Output A
Not Used – Option dependent
Output B
Not Used – Option dependent
Enable
Off – On
Failclass
Alarm (1) – Trip MB (6)
4961
4962
4963
4964
4965
4966
Setpoint
8.0 V – 32.0 V
Delay
0.0 s – 999.0 s
Output A
Not Used – Option dependent
Output B
Not Used – Option dependent
Enable
Off – On
Failclass
Alarm (1) – Trip MB (6)
4240 W. fail 102
4540 Run feedb. fail
4960 U< aux. term. 1
4970 U> aux. term. 1
4980 U< aux. term.98
4550 MPU wirebreak
4370 W. fail 105
4500 W. fail 108
4520 Overspeed 2
4531 Setpoint
0 rpm – 4000 rpm
4532 Delay
0.0 s – 20.0 s
4533 Output A
Not Used – Option dependent
4534 Output B
Not Used – Option dependent
4530 Crank failure
12.0 V – 36.0 V
0.0 s – 999.0 s
Not Used – Option dependent
Not Used – Option dependent
Off – On
Alarm (1) – Trip MB (6)
4991 Setpoint
4992 Delay
4993 Output A
4994 Output B
4995 Enable
4996 Failclass
4990 U> aux. term.98
5**1 Function
Alarm – Limit – Horn
5**2 Off Delay
0.0 s – 999.9 s
** = 00, 01, 02, 03, 04, 05, 06, 11, 12, 13, 14
5**0 Relay **