- 59 -
Power management setup
Note: Possible failclasses: Alarm (1) - Warning (2) - Trip GB (3) - Trip & Stop (4) - Shutdown (5) - Trip MB (6)
8001 Setpoint
0kW – 20000 kW
8002 Timer
0.0 s – 90.0 s
8003
Minimum load
0kW – 20000 kW
8111 Priority adjustment
1h – 20000h
8112 Type
Absolute run hours –
Relative run hours
8113
Reset relative counter
Off – On
8121 Output A
Not Used – Option dependent
8122 Output B
Not Used – Option dependent
8123
Enable
Off – On
8141 Timer
10 s – 600.0 s
8011 Setpoint
0kW – 20000 kW
8012 Timer
5.0 s – 990.0
8031 Priority
Manual
Running hours
Fuel optimisation
8032 Multistart set 1
1 – 16
8033
Min. running set 1
1 – 16
8034
Multistar config.
Off – On
8035
Multistart set 2
1 – 16
8036
Min. running set 2
1 – 16
8021 DG's available
1 – 16
8022 Mains available
No mains
Single mains
Multiple mains
8023
PMS active
Off – On
8024
Start/Stop
Remote
Local
Timer
8025
Command Unit
Off – On
8171 Setpoint
30.0% – 100.0%
8172 Swap setp.
50kW – 20000 kW
8173
Timer
0.0 s – 999.0 s
8174
Hours
1h – 20000 h
8175
Enable
Off – On
82*1 Setpoint
10kW – 20000 kW
82*2 Timer
1.0 s – 999.9 s
82*3
Output A
Not Used – Option dependent
82*4
Output B
Not Used – Option dependent
82*5
Enable
Off – On
80*1 ID1
Off – On
80*2 ID2
Off – On
80*3
ID3
Off – On
80*4
ID4
Off – On
80*5
ID5
Off – On
80*6
ID6
Off – On
8**1 P1
1 – 16
8**2 P2
1 – 16
8**3
P3
1 – 16
8**4
P4
1 – 16
8**5
P5
1 – 16
8**6
Tx
Off – On
* = 4, 5, 6, 7
* = 08, 09, 10
* = 2, 3, 4, 5, 6
8000 Load dep. start
80*0 Number of IDs 8140 Stop non-con. DG
8170 Fuel optimize
82*0 Avail. power*
8**0 Priority
8110 Running hours
8120 Ground relay
8010 Load dep. stop
8020 PMS config.
8030 Priority select