- 79 -
Check tightness of nuts and bolts x x
Grease door hinges and locks x x
Change lubrication oil
(3)
xxx
Replace oil filter(s)
(3)
xxx
Replace air filter element
(4) xxx
Grease mechanical links (e.g. fuel solenoid link) x x x
Measure alternator insulation resistance (See (*) Measuring the
alternator insulation resistance)
xxx
Check glycol level in coolant
x xx
Check pH level of coolant
x
xx
Replace and drain fuel pre-filter/Water separator xx
Replace fuel filter element xx
Check crankcase pressure xx
Check fixation of hoses, cables and pipes xx
Replace drive belt(s) x
Replace safety cartridge x
Clean and inspect turbocharger impeller and housing x
Lubricate fan hub bearings x
Check fueltank for water (5) x
Inspection by Atlas Copco Service technician
Generators in standby application have to be tested on a regular
basis. At least once a month the engine should run for one hour. If
possible a high load (> 30%) should be applied so that the engine
reaches its operating temperature.