6. Fit actuator. If required, slightly turn actuator until splines of coupling engage.
Figure 14:
Information
Ensure that the spigot (if provided) fits uniformly in the recess and that the flanges
are in complete contact.
7. If flange bores do not match thread:
7.1 Slightly rotate handwheel until bores line up.
7.2 If required, shift actuator by one tooth on the coupling.
8. Fasten actuator with screws.
Information: We recommend applying liquid thread sealing material to the
screws to avoid contact corrosion.
9. Fasten screws crosswise to a torque according to table.
Table 9:
Tightening torques for screws
Tightening torque [Nm]Threads
Strength class A2-80/A480
10M6
24M8
48M10
82M12
200M16
392M20