6.1.1. End stop CLOSED: set
1.
Loosen nut [1] and turn slightly in opposite direction.
Figure 12:
2.
Turn valve via handwheel to end position CLOSED. (also refer to: page 21,
Manual valve operation)
Figure 13:
3. If end position CLOSED has not been reached: Turn back setting screw [2]
until the valve can be operated into end position CLOSED.
Information:
Avoid excessive unscrewing of settings screw [2]. Respect maximum distance
between screw head and housing wall. Refer to: page 17, Dimensions of
setting screws for setting the end stops
Figure 14:
4. If the valve is in end position CLOSED: Turn setting screw [2] up to the stop.
This completes the setting of end stop CLOSED.
5. Hold setting screw [2] and tighten nut [1] until it is flush on the housing. Firmly
tighten nut [1] using a spanner.
Information: The setting screw [2] must not turn when tightening the nut [1]:
Otherwise the end stop setting will be changed.
Having completed this procedure, end position switch CLOSED can be immediately
set. page 19, Limit switching: set
6.1.2. End stop OPEN: set
If the end stop CLOSED has already been set, setting of the end position OPEN
is generally not required.
16
EQ 40 EQ 150
Commissioning EQ 300 EQ 600