Features and functions
Auxiliary voltage 24 V DC: max. 100 mA for supply of control inputs, galvanically isolated
from internal voltage supply.
Standard:Voltage output
Auxiliary voltage 115 V AC: max. 30 mA for supply of control inputs, galvanically isolated
from internal voltage supply
(Not possible in combination with PTC tripping device)
Option:
Redundant line topology with universal redundancy behaviour according to AUMA redundancy I or II
Redundant loop topology in combination with SIMA Master Station
Max. number of actuators with actuator controls per redundant loop: 247 units
Max. possible cable length between the actuators equipped with actuator controls without external
repeater: 1,200 m
Max. possible total length per redundant ring: approx. 290 km
Automatic commissioning of the redundant ring by means of the SIMA Master Station
Redundancy (option)
Connector types: ST or SC connector
FO cables
-
Multi-mode: 62,5(50)/125 µm, range approx. 2.5 km (max. 2.0 dB/km)
-
Single-mode: 9/125 µm, range approx. 15 km (max. 0.4 dB/km)
Topologies: Line, star and redundant ring (with single-channel Modbus RTU interface)
Baud rate: up to 115.2 kbit/s
Optical budget:
-
Multi-mode: 13 dB
-
Single-mode: 17 dB
Wave length: 1,310 mm
FO coupler by EKS required at DCS, reference addresses: AUMA or www.eks-engel.com
FO cable connection (option)
Selector switch: LOCAL - OFF - REMOTE (lockable in all three positions)
Push buttons OPEN, STOP, CLOSE, RESET
-
Local STOP
The actuator can be stopped via push button STOP of local controls if the selector
switch is in position REMOTE. (Not activated when leaving the factory.)
6 indication lights:
-
End position and running indication CLOSED (yellow), torque fault CLOSE (red),
motor protection tripped (red), torque fault OPEN (red), end position and running
indication OPEN (green), Bluetooth (blue)
Graphic LC display: illuminated
Standard:Local controls
Special colours for the indication lights:
-
End position CLOSED (green), torque fault CLOSE (blue), torque fault OPEN
(yellow), motor protection tripped (violet), end position OPEN (red)
Option:
Bluetooth class II chip, version 2.1: With a range up to 10 m in industrial environments, supports the
SPP Bluetooth profile (Serial Port Profile).
Required accessories:
AUMA CDT (Commissioning and Diagnostic Tool for Windows-based PC)
AUMA Assistant App (Commissioning and Diagnostic Tool for Android devices)
Bluetooth
Communication interface
83
SA 07.2 SA 16.2/SAR 07.2 SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Modbus RTU Technical data