Features and functions
Selectable type of seating, limit or torque seating for end position OPEN and end po-
sition CLOSED
Torque by-pass: Adjustable duration (with adjustable peak torque during start-up time)
Start and end of stepping mode as well as ON and OFF times can be set individually
for directions OPEN and CLOSE, 1 to 1,800 seconds
Any 8 intermediate positions: can be set between 0 and 100 %, reaction and signal
behaviour programmable
Running indication blinking: can be set
Positioner
-
Position setpoint via Modbus RTU interface
-
Programmable behaviour on loss of signal
-
Automatic adaptation of dead band (adaptive behaviour selectable)
-
Split range operation
-
Change-over between OPEN-CLOSE control and setpoint control possible via
fieldbus interface
Standard:Application functions
PID process controller: with adaptive positioner, via 0/4 20 mA analogue inputs for
process setpoint and actual process value
Multiport valve: Up to 16 positions, signals (pulse or edge), accuracy < 0.2 %
Automatic deblocking: Up to 5 operation trials, travel time in opposite direction can be
set
Static and dynamic torque recording for both rotation directions with torque measure-
ment flange as additional accessory
Options:
EMERGENCY operation (programmable behaviour)
-
Via additional input (option, low active) or via fieldbus interface
-
Reaction can be selected: Stop, run to end position CLOSED, run to end position
OPEN, run to intermediate position
-
Torque monitoring can be by-passed during EMERGENCY operation
-
Thermal protection can be by-passed during EMERGENCY operation (only in
combination with thermoswitch within actuator, not with PTC thermistor).
Standard:Safety functions
Release of local controls via fieldbus interface.Thus, actuator operation can be enabled
or disabled via push buttons on local controls.
Local STOP
-
The actuator can be stopped via push button Stop of local controls if the selector
switch is in position REMOTE. (Not activated when leaving the factory.)
Interlock for main/by-pass valve: Enabling the operation commands OPEN or CLOSE
via fieldbus interface
EMERGENCY Stop push button (latching): interrupts electrical operation, irrespective
of the selector switch position.
PVST (Partial Valve Stroke Test): programmable to check the function of both actuator
and actuator controls: Direction, stroke, operation time, reversing time
Options:
Valve overload protection: adjustable, results in switching off and generates fault signal
Motor temperature monitoring (thermal monitoring): results in switching off and generates fault indic-
ation
Monitoring the heater within actuator: generates warning signal
Monitoring of permissible on-time and number of starts: adjustable, generates warning signal
Operation time monitoring: adjustable, generates warning signal
Phase failure monitoring: results in switching off and generates fault signal
Automatic correction of rotation direction upon wrong phase sequence (3-ph AC current)
Monitoring functions
Electronic device ID with order and product data
Logging of operating data: A resettable counter and a lifetime counter each for:
-
Motor running time, number of starts, torque switch trippings in end position CLOSED, limit
switch trippings in end position CLOSED, torque switch trippings in end position OPEN, limit
switch trippings in end position OPEN, torque faults CLOSE, torque faults OPEN, motor protection
trippings
Time-stamped event report with history for setting, operation and faults
Status signals according to NAMUR recommendation NE 107: "Failure", "Function check", "Out of
specification", "Maintenance required"
Torque characteristics (for version with MWG in actuator):
-
3 torque characteristics (torque-travel characteristic) for opening and closing directions can be
saved separately.
-
Torque characteristics stored can be shown on the display.
Diagnostic functions
84
SA 07.2 SA 16.2/SAR 07.2 SAR 16.2 Control unit - electromechanical
Technical data AC 01.2 Intrusive Modbus RTU