The swing angle set in the factory is indicated on the name plate.
In the standard version the swing angle can be adjusted within the range of 80° to
110°. Optional swivel ranges: refer to technical data pertaining to the order.
9.2.1 Swing angle: modify
Figure 66: End stop
[1] Grub screw
[2] End stop nut
[3] Protective cap
[4] Travelling nut
[5] Sealing ring
1. Unfasten protective cap [3].
2. While holding end stop nut [2] in position with open end spanner, unfasten grub
screw [1].
3. Swing angle increase:
3.1 Turn end stop nut [2] counterclockwise. Do not exceed dimension A
max.
A max. [mm]Type
22SGExC 05.1
22SGExC 07.1
17SGExC 10.1
23SGExC 12.1
3.2 Move valve manually to the desired end position OPEN.
3.3 Turn end stop nut [2] clockwise until it is tight up to the travelling nut [4].
4. Swing angle reduction:
4.1 Move valve manually to the desired end position OPEN.
4.2 Turn end stop nut [2] clockwise until it is tight up to the travelling nut [4].
Do not fall below dimension A min.
A min. [mm]Type
10SGExC 05.1
10SGExC 07.1
08SGExC 10.1
12SGExC 12.1
5. Degrease mounting face of grub screw [1].
46
SGExC 05.1 – SGExC 12.1 Control unit: electromechanic
Commissioning (basic settings) ACExC 01.2 Intrusive Modbus RTU