12.2 Features and functions of actuator controls
For mains voltage and mains frequency, refer to name plates at the controls and the motor
Permissible variation of the mains voltage: ±10 %
Permissible variation of the mains frequency: ±5 %
Option: Permissible variation of the mains voltage: ±30 %
Power supply
Mains frequency
24 V DC +20 % / –15 %
Current consumption: Basic version approx. 250 mA, with options up to 500 mA
The external power supply must have a reinforced insulation against the mains voltage in
accordance with IEC 61010-1 and may only be supplied by a circuit limited to 150 VA in ac-
cordance with IEC 61010-1.
External supply of the electro-
nics (option)
Current consumption of the controls depending on the mains voltage:
For permissible variation of mains voltage by ±10 %:
●
100 to 120 V AC = max. 740 mA
●
208 to 240 V AC = max. 400 mA
●
380 to 500 V AC = max. 250 mA
●
515 to 690 V AC = max. 200 mA
For permissible variation of mains voltage by ±30 %:
●
100 to 120 V AC = max. 1,200 mA
●
208 to 240 V AC = max. 750 mA
●
380 to 500 V AC = max. 400 mA
●
515 to 690 V AC = max. 400 mA
Motor current consumption: Refer to motor name plate
Current consumption
Category III according to IEC 60634-4-443Overvoltage category
The controls are designed for the rated motor power, refer to motor name plateRated power
Standard:
Reversing contactors (mechanically and electrically interlocked) for motor power up to power
class A1
Options:
●
Thyristor unit for mains voltage up to 500 V AC (recommended for modulating actuators)
for AUMA power class B1
Switchgear
1) 2)
Via Modbus RTU interfaceControl
●
Additional inputs, to be assigned as desired:
-
4 digital inputs
-
2 analogue inputs 0/4 – 20 mA
-
Signal transmission is made via fieldbus interface
●
Additional inputs with fixed configuration:
-
6 digital inputs:
-
Control inputs OPEN, STOP, CLOSE, EMERGENCY
-
I/O interface for selecting the control type (fieldbus or additional inputs)
-
MODE for selecting between open-close and modulating duty
-
Analogue input 0/4 – 20 mA for position setpoint (positioner)
Fieldbus interface with additio-
nal inputs (options)
Standard:
24 V DC, current consumption: approx. 10 mA per input
Options:
48 V DC, current consumption: approx. 7 mA per input
60 V DC, current consumption: approx. 9 mA per input
110 V DC, current consumption: approx. 8 mA per input
115 V DC, current consumption: approx. 15 mA per input
115 V AC, current consumption: approx. 15 mA per input
Voltage and current values of
the optional additional inputs
3)
70
SGExC 05.1 – SGExC 12.1 Control unit: electromechanic
Technical data ACExC 01.2 Intrusive Modbus RTU