Figure 70: Torque switching heads
[1] Torque switching head black in direction CLOSE
[2] Torque switching head white in direction OPEN
[3] Lock screws
[4] Torque dials
1. Loosen both lock screws [3] at the indicator disc.
2. Turn torque dial [4] to set the required torque (1 da Nm = 10 Nm).
3. Fasten lock screws [3] again.
Information: Maximum tightening torque: 0.3 0.4 Nm
The torque switch setting is complete.
Example: The figure above shows the following settings:
11.5 da Nm = 115 Nm for direction CLOSE
12.5 da Nm = 125 Nm for direction OPEN
9.7 Limit switching: set
The limit switching records the travel. When reaching the preset position, switches
are operated.
Figure 71: Setting elements for limit switching
Black section:
[1] Setting spindle: End position CLOSED
[2] Pointer: End position CLOSED
[3] Mark: End position CLOSED is set
White section:
[4] Setting spindle: End position OPEN
[5] Pointer: End position OPEN
[6] Mark: End position OPEN is set
9.7.1 End position CLOSED (black section): set
1. Engage manual operation.
2. Turn handwheel clockwise until valve is closed.