To Previous Page IconTo Previous Page
Loading...
9.
Enter password ( enter password).
The screen indicates the pre-set type of seating ( Limit or Torque) by means
of a black triangle .
Change settings
10.
Select new setting Up Down resulting in the following significations:
The symbols have the following meaning:
-
black triangle: = current setting
-
white triangle: = selection (not saved yet)
11.
Confirm selection via Save.
The setting for the type of seating is complete.
12.
Back to step 4 (CLOSED or OPEN): Press Esc .
9.4 Bus address (slave address), baud rate, parity and monitoring time: set
Customer settings M0041
Modbus M0341
MD1 slave address M0247
MD2 slave address M0409
Baud rate M0343
Parity/stop bit M0782
Monitoring time M0781
Default values:
MD1 slave address = 247
MD2 slave address = 247
Baud rate = Auto
Parity/stop Bit = Even, 1 stop bit
Monitoring time = 15 seconds
Information
Parameter MD2 slave address is only available if AUMA redundancy I (option) is
available.
For further settings and information e.g. on redundancy, refer to Manual (Device
integration).
9.5 Switch compartment: open
The switch compartment must be opened to perform the following settings (options).
Flameproof enclosure, danger of explosion!
Risk of death or serious injury.
Before opening, ensure that there is no explosive gas and no voltage.
Handle cover and housing parts with care.
Joint surfaces must not be damaged or soiled in any way.
Do not jam cover during fitting.
48
SGExC 05.1 SGExC 12.1 Control unit: electromechanic
Commissioning (basic settings) ACExC 01.2 Intrusive Modbus RTU