11. Servicing and maintenance
Damage caused by inappropriate maintenance!
Servicing and maintenance must be carried out exclusively by suitably qualified
personnel having been authorised by the end user or the contractor of the plant.
Therefore, we recommend contacting our service.
Only perform servicing and maintenance tasks when the device is switched off.
AUMA
Service & Support
AUMA offer extensive service such as servicing and maintenance as well as customer
product training. For the relevant contact addresses, please refer to <Addresses>
in this document or to the Internet (www.auma.com).
11.1 Preventive measures for servicing and safe operation
The following measures are required to ensure safe device operation:
6 months after commissioning and then every year
Carry out visual inspection:
Cable entries, cable glands, blanking plugs, etc. have to be checked for correct
tightness and sealing.
Respect torques according to manufacturer's details.
Check fastening screws between actuator and gearbox/valve for tightness. If
required, fasten screws while applying the tightening torques as indicated in
chapter <Assembly>.
When rarely operated: Perform test run.
For enclosure protection IP 68
After continuous immersion:
Check actuator.
In case of ingress of water, locate leaks and repair, dry device correctly and
check for proper function.
11.2 Disconnection from the mains
If the device must be dismantled, e.g. for service purposes, it can be separated from
the mains without having to remove the wiring.
Flameproof enclosure, danger of explosion!
Risk of death or serious injury.
Before opening, ensure that there is no explosive gas and no voltage.
Handle cover and housing parts with care.
Joint surfaces must not be damaged or soiled in any way.
Do not jam cover during fitting.
65
SGExC 05.1 SGExC 12.1 Control unit: electromechanic
ACExC 01.2 Intrusive Modbus RTU Servicing and maintenance