Manual drive for setting and emergency operation, handwheel does not rotate during electrical
operation.
Option: Handwheel lockable
Manual operation
AUMA plug/socket connector with screw-type connectionConnection to controls
Standard: Coupling without bore
Options: Machined coupling with bore and keyway, square bore or bore with two-flats accor-
ding to EN ISO 5211
Coupling
Dimensions according to EN ISO 5211Valve attachment
For nominal voltage and 20 °C ambient temperature and an average load with running torque or modulating torque according to sepa-
rate technical data.The type of duty must not be exceeded.
1)
Technical data for limit and torque switches
2 x 10
6
startsMechanical lifetime
Silver plated contacts:
30 V AC/DCU min.
250 V AC/DCU max.
20 mAI min.
5 A at 250 V (resistive load)
3 A at 250 V (inductive load, cos phi = 0.6)
I max. AC current
0.4 A at 250 V (resistive load)
0.03 A at 250 V (inductive load, L/R = 3 µs)
7 A at 30 V (resistive load)
5 A at 30 V (inductive load, L/R = 3 µs)
I max. DC current
Gold plated contacts:
5 VU min.
30 VU max.
4 mAI min.
400 mAI max.
Technical data for blinker transmitter
10
7
startsMechanical lifetime
Silver plated contacts:
10 V AC/DCU min.
250 V AC/DCU max.
3 A at 250 V (resistive load)
2 A at 250 V (inductive load, cos phi 0.8)
I max. AC current
0.25 A at 250 V (resistive load)I max. DC current
69
SGExC 05.1 SGExC 12.1 Control unit: electromechanic
ACExC 01.2 Intrusive Modbus RTU Technical data