Standard:
Via Modbus RTU interface
Options:
Additional, programmable output contacts (only possible in combination with additional inputs):
6 programmable output contacts:
-
5 potential-free NO contacts with one common, max. 250 V AC, 1 A (resistive load)
Default configuration: End position CLOSED, end position OPEN, selector switch in
REMOTE, torque fault CLOSE, torque fault OPEN
-
1 potential-free change-over contact, max. 250 V AC, 5 A (resistive load)
Default configuration: Collective fault signal (torque fault, phase failure, motor protec-
tion tripped)
6 programmable output contacts:
-
5 change-over contacts with one common, max. 250 V AC, 1 A (resistive load)
-
1 potential-free change-over contact, max. 250 V AC, 5 A (resistive load)
6 programmable output contacts:
-
6 potential-free change-over contacts without one common, per contact max. 250 V
AC, 5 A (resistive load)
Status signals
Standard:
Via Modbus RTU interface
Option
Galvanically isolated position feedback E2 = 0/4 20 mA (load max. 500 Ω), only possible
in combination with output contacts
Position feedback signal
Standard:
Auxiliary voltage 24 V DC, max. 100 mA for supply of the control inputs, galvanically isolated
from internal voltage supply
Option:
Auxiliary voltage 115 V AC, max. 30 mA to supply the control inputs
4)
, galvanically isolated
from internal voltage supply
Voltage output
Redundant line topology with universal redundancy behaviour according to AUMA redundancy
I or II
Redundant loop topology in combination with the SIMA Master Station
Max. number of actuators equipped with AUMATIC controls per redundant loop: 247
units
Max. possible cable length between the actuators equipped with controls without external
repeater: 1,200 m.
Max. possible total length per redundant loop: approx. 290 km
Automatic commissioning of the redundant loop by means of the SIMA Master Station
Redundancy (option)
Standard:
Selector switch LOCAL - OFF - REMOTE (lockable in all three positions)
Push buttons OPEN, STOP, CLOSE, RESET
6 indication lights:
-
End position CLOSED (yellow), torque fault CLOSE (red), motor protection tripped
(red), torque fault OPEN (red), end position and running indication OPEN (green),
Bluetooth (blue)
Graphic LC display, illuminated
Options:
Special colours for the 5 indication lights:
-
End position CLOSED (green), torque fault CLOSE (blue), torque fault OPEN (yellow),
motor protection tripped (white), end position OPEN (red)
Local controls
Bluetooth class II chip, version 2.0 with a range up to 10 m in industrial environments. Supports
the SPP Bluetooth profile (Serial Port Profile).
Programming software:
AUMA ToolSuite, commissioning and diagnostic tool for windows based PCs, PDAs and
smart phones
Bluetooth
Communication interface
71
SGExC 05.1 SGExC 12.1 Control unit: electromechanic
ACExC 01.2 Intrusive Modbus RTU Technical data