Flameproof enclosure, danger of explosion!
Risk of death or serious injury.
Before opening, ensure that there is no explosive gas and no voltage.
Handle cover and housing parts with care.
Joint surfaces must not be damaged or soiled in any way.
Do not jam cover during fitting.
Danger of corrosion due to damage to paint finish!
Touch up damage to paint finish after work on the device.
1. Unfasten motor cover [1].
2. Set required operating time via potentiometer [2].
3. Clean sealing faces of motor cover and housing.
4. Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the sealing faces.
5. Preserve joint surfaces with an acid-free corrosion protection agent.
6. Check whether O-ring is in good condition, correctly insert O-ring.
7. Fit motor cover [1] and fasten with screws (tightening torque approx. 50 Nm).