Table 13: Faults and warnings via status indications in the display
For indicated value > 0:Description/causeIndication on display
Press push button Details.
For details, refer to <Warnings and Out of
specification> table.
Collective signal 02:
Indicates the number of active warnings.
Warnings S0005
Press push button Details.
For details, refer to <Not ready REMOTE and
Function check> table.
Collective signal 04:
Indicates the number of active signals.
Not ready REMOTE S0006
Press push button Details to display a list
of detailed indications.
For details, refer to <Faults and Failure> table.
Collective signal 03:
Indicates the number of active faults.
The actuator cannot be operated.
Fault S0007
Press push button Details.
For details refer to <Warnings and Out of
specification> table.
Collective signal 07:
Indication according to NAMUR recommenda-
tion NE 107
Actuator is operated outside the normal ope-
ration conditions.
Out of specification S0008
Press push button Details.
For details, refer to <Not ready REMOTE and
Function check> table.
Collective signal 08:
Indication according to NAMUR recommenda-
tion NE 107
The actuator is being worked on; output si-
gnals are temporarily invalid.
Function check S0009
Press push button Details to display a list
of detailed indications.
Collective signal 09:
Indication according to NAMUR recommenda-
tion NE 107
Recommendation to perform maintenance.
Maintenance required S0010
Press push button Details to display a list
of detailed indications.
For details, refer to <Faults and Failure> table.
Collective signal 10:
Indication according to NAMUR recommenda-
tion NE 107
Actuator function failure, output signals are
invalid
Failure S0011
Table 14: Warnings and Out of specification
RemedyDescription/causeIndication on display
Press push button Details to display a list
of individual indications.
For a description of the individual signals, refer
to Manual (Operation and setting).
Collective signal 06:
Possible cause:
Configuration setting is incorrect.
The device can still be operated with restricti-
ons.
Config. warning
Press push button Details to display a list
of individual indications.
For a description of the individual signals, refer
to Manual (Operation and setting).
Collective signal 15:
Device warnings
The device can still be operated with restricti-
ons.
Internal warning
Check 24 V DC voltage supply.The external 24 V DC voltage supply of the
controls has exceeded the power supply limits.
24 V DC external
Check modulating behaviour of actuator.
Check parameter Perm. running time/h
M0356, re-set if required.
Warning on time max. running time/h excee-
ded
Wrn on time running
Check modulating behaviour of actuator.
Check parameter Permissible starts/h
M0357, re-set if required.
Warning on time max. number of motor starts
(starts) exceeded
Wrn on time starts
Verify signals:
Setpoint E1
Actual value E2
Actual process value E4
Check connection to master.
The failure behaviour is active since all requi-
red setpoints and actual values are incorrect.
Failure behav. active
Check wiring.Warning: Loss of signal analogue input 1
Wrn input AIN 1
Check wiring.Warning: Loss of signal analogue input 2
Wrn input AIN 2
59
SGExC 05.1 SGExC 12.1 Control unit: electromechanic
ACExC 01.2 Intrusive Modbus RTU Corrective action