2 Electrical Specifications
2 ELECTRICAL SPECIFICATIONS
2.1 Classifications
Classification according to BS EN298:2012
Mains
Supply:
Single phase 230V, +10%/-15%}
47-63 Hz, unit max. consumption 140W
Single phase 120V, +10%/-15%}
Climate: Min. Temperature 0
O
C (32
O
F)
Recommended Temperature Less than 40
O
C (104
O
F)
Max. Temperature 60
O
C (140
O
F)
Humidity 0 to 90% non-condensing
Storage: Temperature -20 to 85
O
C (-4 to 185
O
F)
Protection
Rating:
The unit is designed to be panel mounted in any orientation and the front facia is IP65,
NEMA4. The back of the unit is IP20, NEMA1.
2.2 Inputs and Outputs
MM Inputs and Outputs
230V Unit:
Outputs Terminal 57 250mA Must be connected through contactor
Max Load 6A
58 250mA Must be connected through contactor
59 1A 0.6 power factor
60 1A 0.6 power factor
61 1A 0.6 power factor
62 1A 0.6 power factor
63 1A 0.6 power factor
78 100mA To drive relay only – switched neutral
79 100mA To drive relay/lamp only – switched neutral
120V Unit:
Outputs Terminal 57 250mA Must be connected through contactor
Max Load 6A
58 250mA Must be connected through contactor
59 2A 0.6 power factor
60 2A 0.6 power factor
61 2A 0.6 power factor
62 2A 0.6 power factor
63 2A 0.6 power factor
78 100mA To drive relay only – switched neutral
79 100mA To drive relay/lamp only – switched neutral