In addition to when there is a setting conflict, the MM will be forced into commission mode if any of the
forced commission reason occurs.
Forced Commission Message
Fuel not commissioned.
Selected fuel must be commissioned.
Servo configuration does not match commissioning.
Option 8 and/or expansion option 80 do not match the last commission settings.
VSD configuration does not match commissioning.
VSD settings for channels 5 and 6 must be the same as the last commission settings.
Golden start optioned but not commissioned.
Commission golden start position (see section 3.4.8).
FGR optioned but not commissioned.
Commission FGR start position (see section 3.4.9).
Trim channel does not match commissioning.
Option 76 trim channel must be the same as the last commission settings.
Fuel/air-rich trim ranges changed.
Parameter 13 and/or parameter 19 do not match last commission settings.
BC Option/parameter mismatch.
BC options 110 – 160 must be set the same as their corresponding parameters.
Invalid option value.
An option value is outside the allowed range.
Invalid parameter value.
A parameter value is outside the allowed range.
Invalid expansion option value.
An expansion option value is outside the allowed range.
Options have been reset.
Option settings have been reset due to data lost in an EEPROM error.
Parameters have been reset.
Parameter settings have been reset due to data lost in an EEPROM error.
Expansion options have been reset.
Expansion option settings have been reset due to data lost in an EEPROM error.
VPS sensor not commissioned.
Gas pressure sensor has been enabled but not commissioned.
Commissioned gas pressure during valve proving too low.
Gas pressure stored during valve proving is less than option/parameters 133 and/or 136.
Commissioned running gas pressure too low.
Gas pressure at one or more commissioned points is less than option/parameter 136.
APS sensor not commissioned.
Air pressure has been enabled but not commissioned.
Commissioned air pressure too low.
Air pressure at one or more commissioned points is less than option/parameters 147 and/or 149.
IR Upload was completed successfully, check configuration then restart.
Check data has uploaded successfully before restarting in run mode.
22.05.2017 Mk8 MM End User Guide Page 62
4 Errors and Lockouts
4.5 Forced Commission Reasons