Alarms and warnings are faults detected with the system operation. If an alarm occurs, the burner will
stop running, and if a warning occurs, the burner will continue to run. The following
options/parameters set whether system operation faults are set as alarms or warnings:
Option 13 EGA Fault Response
Option 14 Warning Response
Expansion Option 9 Burner Operation at High Water
Expansion Option 20 Burner Operation on Feed water Control Fault
Expansion Option 88 Action on Pressure Sensor Fault
Fault Message Description
1 EGA Internal Error Fault on EGA
Alarm or warning depending on option 13
Check EGA for fault description
2 No EGA Communications MM has lost communications with EGA
Alarm or warning based on option 13 (warning if option 12 is set to monitoring only)
Check parameter 10 is set to correct EGA version
Check EGA operating mode is selected as ‘EGA with MM’
Check wiring between EGA and MM (terminals 25 and 26 on MM)
3 O2 Upper Limit O2 value is above upper limit offset of commissioned value*
Alarm or warning depending on option 13
Check exhaust gas readings and option 19
4 O2 Absolute Limit O2 value is below absolute limit*
Alarm or warning depending on option 13
Check exhaust gas readings and option 25
5 O2 Lower Limit O2 value is below lower limit offset of commissioned value*
Alarm or warning depending on option 13
Check exhaust gas readings and option 22
6 CO2 Upper Limit CO2 value is above upper limit offset of commissioned value*
Alarm or warning depending on option 13
Check exhaust gas readings and option 20
7 CO2 Absolute Limit CO2 value is above absolute limit*
Alarm or warning depending on option 13
Check exhaust gas readings and option 26
8 CO2 Lower Limit CO2 value is below lower limit offset of commissioned value*
Alarm or warning depending on option 13
Check exhaust gas readings and option 23
9 CO Upper Limit CO value is above upper limit offset of commissioned value*
Alarm or warning depending on option 13
Check exhaust gas readings and option 21
10 CO Absolute Limit CO value is above absolute limit*
Alarm or warning depending on option 13
Check exhaust gas readings and option 27
11 NO Upper Limit NO value is above upper limit offset of commissioned value*
Alarm or warning depending on option 13
Check exhaust gas readings and parameter 94
Page 49 Mk8 MM End User Guide 22.05.2017
4 Errors and Lockouts
4.3 Alarms and Warnings