Loading...
3 End User Operation
3.1.2 Faults
Figure 3.1.2.i Lockouts
Press in the Home screen to view the faults, which are categorised into lockouts, errors,
alarms, warning and first out alarms, and are access by pressing on the corresponding tabs.
Fault Type Shuts Down Burner Reset By
Lockout Burner control fault Yes Reset button or input on T56
Error Internal or hardware fault Yes Power cycle
Alarm Critical system fault Yes Reset button or input
Warning Non-critical fault No Reset button
First out Configurable fault Optional Reset button/ auto
Page 12 Mk8 MM End User Guide 22.05.2017