Conflicts
Some of the options, parameters and expansion options may require another option, parameter or
expansion option to be set. Please see the below table for these settings conflicts. A setting conflict will
result in the MM being forced in to Commission mode.
Setting Conflict Message
(1) (P53, P54, P55, P56) External load sensor incorrectly configured
The external load sensor must be set with the minimum and maximum values and voltages.
Check option 1 and parameters 53 – 56.
(1) (81, 83) OTC setpoints too high for optioned load sensor
If minimum and maximum setpoints OTC setpoints must be set within the possible range of the
optioned load detector.
Check option 1, 81 and 83.
(9) (45) Internal stat must be disabled if load sensor not present
If external modulation is enabled without a load sensor, the internal stat must always be closed.
Check options 9 and 45.
(30) (31) Invalid remote sepoint configuration
The Minimum Remote Setpoint (DTI/Modbus/External) cannot be set higher than the Maximum
Remote Setpoint (DTI/Modbus/External) and vice versa.
Check options 30 and 31.
(43) (44) (E1) Water level control only be on the multi-burner master
Water level control should only be enabled on the master (multi-burner ID 1 set in option 44),
when using the multi-burner function.
Check options 43 ,44 and expansion option 1.
(43) (44) (16) Sequencing only be only the multi-burner master
Only the master (multi-burner ID 1 set in option 44) can be set for sequencing.
Check options 16, 43 and 44.
(43) (44) (12) EGA and trim can only be on the multi-burner master
Only the master (multi-burner ID 1 set in option 44) can be optioned with an EGA.
Check options 12, 43 and 44.
(43) (44) (E110) Firstouts can only be on the multi-burner master
Only the master (multi-burner ID 1 set in option 44) can have first outs enabled.
Check options 43, 44 and expansion option 110.
(43) (44) (E120) Heat-flow can only be on the multi-burner master
Only the master (multi-burner ID 1 set in option 44) can have heat flow function enabled.
Check options 43, 44 and expansion option 120.
(43) (44) (45) External modulation can only be on the multi-burner master
Only the master (multi-burner ID 1 set in option 4) can be set for external modulation.
Check options 43 – 45.
(43) (44) (E82) Draught control can only be on the multi-burner master.
Only the master (multi-burner ID 1 set in option 4) can be set for draught control.
Check options 43 and 44, and expansion option 82.
(43) (57) Fuel flow metering must be enabled for multi-burner
The multi-burner function requires fuel flow metering.
Check options 43 and 57.
(43) (135) NFPA Post Purge cannot be optioned with multi-burner
The multi-burner function can only use standard, not NFA post purge.
Check option 43 and option/parameter 135.
Page 57 Mk8 MM End User Guide 22.05.2017