Forced Commission Message
Options and/or parameters reset to default values. Check configuration then restart.
Reset of setting using option/parameter 160. Set/check settings and restart.
First outs are optioned but not configured. Check configuration then restart.
Configure first outs and restart.
Too many sensors require commissioning.
Gas and air pressure sensors can be optioned on after fuel has been commissioned, but only one a
time before completing commissioning process for each.
Draught servo minimum angle greater than a commissioned draught servo angle.
One or more commissioned points for draught servomotor is lower than expansion option 83.c
Capacitance probe not commissioned.
Capacitance probe has been enabled but not commissioned.
Capacitance probe serial number does not match commissioning.
Capacitance probes have changed, recommission water level.
External level sensor not commissioned.
External level sensor has been enabled but not commissioned.
VSD1 Feedback variation too small. Maximum VSD fault tolerance is ---
Difference between smallest and largest channel 5 VSD feedback is less than option 99 (this
message will display required value for option 99 to run).
VSD 2 Feedback variation too small. Maximum VSD fault tolerance is ---
Difference between smallest and largest channel 6 VSD feedback is less than option 109 (this
message will display a required value for option 109 to run).
Draught control optioned but not commissioned.
Draught control has been enabled but not commissioned.
Fully metered optioned but not commissioned.
Fully metered control has been enabled but not commissioned.
Fully metered configuration does not match commissioning.
One or more sensors used for fully metered control that were not present during commissioning are
now enabled.