GS1 Series AC Drive User Manual
3–11
Chapter 3: Keypad Operation and Quickstart
Source of Operation Command Setting: 0
The AC drive operation will be determined by external control terminals and the
keypad stop is enabled.
Default Setting: 0
Settings 0 Operation Determined by Digital Keypad
1 Operation determined by external control
terminals. Keypad STOP is enabled.
2 Operation determined by external control
terminals. Keypad STOP is disabled.
3 Operation determined by RS485 interface.
Keypad STOP is enabled.
4 Operation determined by RS485 interface.
Keypad STOP is disabled.
Source of Frequency Command Setting: 0
The frequency of the AC drive will be determined by keypad potentiometer.
Default: 0
Settings: 0 Frequency determined by keypad potentiometer
1 Frequency determined by digital keypad up/down
2 Frequency determined by 0 to +10V input on AI
terminal. AI switch must be set to “V”.
3 Frequency determined by 4 to 20mA input on AI
terminal. AI switch must be set to “I”.
4 Frequency determined by 0 to 20mA input on AI
terminal. AI switch must be set to “I”.
5 Frequency determined by RS485 communication
interface
4-00
3-00
Switch must be set to
“V” in order to use a 0
to +10V input
Switch must be set to
“I” in order to use a 4
to 20mA input
Switch must be set to
“I” in order to use a 0
to 20mA input