6 Parameter Settings and Functions
© Copyright Reserved Autonics Co., Ltd. 67
6.4.7 Alarm output delay
Alarm output delay can be set to prevent false alarms caused by erroneous input signals
resulting from disturbances or noise.
With a preset delay time, alarm output does not turn on for the preset duration. Instead, the
concerned alarm indicator on the front will flash in 0.5-second intervals.
Alarm ON delay time: Stands by for the preset duration upon an alarm event, checks the
alarm trigger conditions, and turns on the alarm output if the conditions are still present.
Alarm OFF delay time: Stands by for the preset duration following alarm output off, checks
the alarm trigger conditions, and turns off the alarm output if the deactivation conditions are
still present.
Setting
group
Parameter
Setting
range
Factory default Unit
Alarm Setting
Alarm ON Delay Time 0 to 3600 0 Sec.
Alarm OFF Delay 0 to 3600 0 Sec.