6 Parameter Settings and Functions
© Copyright Reserved Autonics Co., Ltd. 69
6.4.8.1 LBA monitoring time
You can set the LBA monitoring time to check changes in the control subject's temperature.
Automatically setting with auto-tunning.
Regardless of alarm output operation mode (Alarm Mode) (including LBA monitoring time
as “0”), after running auto-tuning, the integration time×2 value is saved automatically.
(If SV is out of the range of auto setting, it is set as max. or min. value of auto setting.)
Except input type changing, re-running auto-tuning, manual setting of LBA monitoring time,
it maintains the present SV.
Auto setting range: 0020 to 9999
Setting group Parameter Setting range
Unit
Alarm Setting
LBA Time Ch1,
LBA Time Ch2
0000 to 9999 0 Sec
6.4.8.2 LBA detection band
You can set the minimum value of deviation change to decrease during LBA monitoring time.
Automatically setting with auto-tunning.
Regardless of alarm output operation mode (Alarm Mode) (including LBA monitoring time
as “0”), after running auto-tuning, the integration time×2 value is saved automatically.
Except input type changing, re-running auto-tuning, manual setting of LBA monitoring time,
it maintains the present SV.
(If SV is out of the range of auto setting, it is set as max. or min. value of auto setting.)
Auto setting range
Temperature L: 002.0 to 100.0 (℃/℉)
Temperature H: 0002 to 010.0 (℃/℉)
Setting group Parameter Setting range
Unit
Alarm Setting
LBA Band Ch1,
LBA Band Ch2
0 to 999 (H)
0.0 to 999.9 (L)
2
℃/℉