Service Commands
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FO/FE Rev. E, 021105,
Autronica Fire and Security AS
Page 114
14.5.3 Enable Loop
This menu allows you to enable one loop (a selected loop) at a time
without interrupting the system.
Step Actions to be taken Display Indication
1
To enter the Main Menu, press
!
MENU
19:23
Total: 3
1 SHOW STATUS
2 DISABLE
3 ENABLE
4 SYSTEM
5 SERVICE
2
To select SERVICE, press 5.
SERVICE
19:23
1 TEST
2 LOG
3 LOOP COMMANDS
4 OIL&GAS INHIBIT
SERVICE
19:23
1 TEST
2 LOG
3 LOOP COMMANDS
4 OIL&GAS INHIBIT
3
To select LOOP COMMANDS, press 3.
SERVICE
19:23
LOOP COMMANDS
1 CLEAR TOPOLOGY
2 DISABLE LOOP
3 ENABLE LOOP
SERVICE
19:23
LOOP COMMANDS
1 CLEAR TOPOLOGY
2 DISABLE LOOP
3 ENABLE LOOP
4
To select ENABLE LOOP, press 3.
SERVICE
19:23
BSB 310
BSJ 310
BSL 310
ENABLE LOOP
5
Use the keyboard to enter text into the input box
-
OR ,- as shown in this example:
To select a Loop Name, press
then scroll downwards by pressing
9
YZ
or move up again by pressing
6
PQR