In the Event of a Fire Alarm -
with Alarm Delay
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FO/FE Rev. E, 021105,
Autronica Fire and Security AS
Page 37
6.2 Actions to be Taken - Fire Alarm with Alarm Delay
Step Actions to be taken Display Indication Audible Indication
1
Follow all precautions
described in the local
fire instructions, step by
step.
The internal buzzer on
the operator panel is
turned on.
Comments:
The red FIRE indicator starts to blink.
The FUNCTION DELAYED and FUNCTION DISABLED indicators have a
steady yellow light indicating that Immediate Output Actioning has been
disabled (manual operation in Menu Mode).
In this example, one point in a Delayed Action detection zone is signalling an
alarm.
The message «SHOW SUPPR. INFO» is shown in the lower right corner,
indicating that a disablement exists (Immediate Output Actioning has been
disabled). One or several fire warnings, tests or faults may also exist. To
view suppressed information, press Action Digit 4 (SHOW SUPPR. INFO).
2
To silence the internal
buzzer, press the black
Mute Panel button
The internal buzzer on
the operator panel is
turned off.
3
Press and observe
the zone(s) in alarm
state in the display.
Comments:
If you want to view detailed zonal/point information, go to step 4. If not, go
directly to step 8.
4
To select a zone (if
there are several
zones), scroll with the
arrow buttons
6
PQR
or
9
YZ
5
To view detailed zonal
information, press
6
To view points in alarm,
press Action Digit 1
(SHOW POINTS).
7
To go two steps
backwards, press
twice.
Comments:
If you want to view detailed information for another zone, select the other
zone in step 4, repeat step 5, 6 and 7, then go to step 8. If not, go directly to
step 8.
If you want to prolong the delay, you can press Enter, then Action Digit 4
(PROLONG DELAY). The T1 period will terminate, and the T2 period will
start. If you do not want to prolong the delay period, go directly to step 9.
1*KITCHEN
FIRST DELAYED OUTPUTS ACTIVATES 14:40
FIRE ALARMS
19:23
Total: 1
2: ACTIVATE 4: SHOW SUPPR. INFO
1*KITCHEN
FIRST DELAYED OUTPUTS ACTIVATES 14:40
FIRE ALARMS
19:23
Total: 1
2: ACTIVATE 4: SHOW SUPPR. INFO
1*KITCHEN
FIRST DELAYED OUTPUTS ACTIVATES 14:40
FIRE ALARMS
19:23
Total: 1
1*KITCHEN
FIRST DELAYED OUTPUTS ACTIVATES 14:40
FIRE ALARMS
19:23
Total: 1
1*KITCHEN
FIRST DELAYED OUTPUTS ACTIVATES 14:40
FIRE ALARMS
19:23
Total: 1
1*KITCHEN
FIRST DELAYED OUTPUTS ACTIVATES 14:40
FIRE ALARMS
19:23
Total: 1
1*KITCHEN
FIRST DELAYED OUTPUTS ACTIVATES 14:40
FIRE ALARMS
19:23
Total: 1
1*KITCHEN
FIRST DELAYED OUTPUTS ACTIVATES 14:40
FIRE ALARMS
19:23
Total: 1
1*KITCHEN
FIRST DELAYED OUTPUTS ACTIVATES 14:40
FIRE ALARMS
19:23
Total: 1
1*KITCHEN
FIRST DELAYED OUTPUTS ACTIVATES 14:40
FIRE ALARMS
19:23
Total: 1