A fire alarm is activated!
Operators Handbook, Fire Alarm Control panel BX-10, P-BX10/FE - Rev.F, 030123, Autronica Fire and Security AS
Page 11
s
ALARM
Test
Fault
Disabled
Power
Zone 1
Zone 2
Zone 3
Zone 4
Alarms
Contr.
Al -outp.
Fault/Disabled/Test
Battery
Power
Earth
Fault
Zone 1
Zone 2
Zone 3
Zone 4
Fault outp.
.
Operator
Imm. alarm
InformationAlarm
System Zone
Operator
1:
2:
3:
4:
Access code: xxx
Silence int. buzzer
Silence/res. alarms
Reset
Autronica Fire & Security
System
0
C
987
6
5
4
3
21
BX-10
R
R
Alarm call activated
4. A fire alarm is activated!
Step Necessary action Visual Warning Status Audio Warning Status
1
Follow local fire instructions
step by step.
The red FIRE indicator
flashes.
The zone indicator(s) at the
bottom-left will flash red,
indicating in which detector
zone(s) the fire is registered
(zones 1 to 4).
The integrated audio warning
device and the sounders are
activated (control outputs are
activated).
2
Cancel internal buzzer by
pressing
The red FIRE indicator and
zone indicator(s) continue to
flash.
The internal audio device is
switched off.
Alarms and control outputs
remain active.
3
Investigate the site of the fire
and take the necessary action.
4
Go into operator mode: key in
operator code +
The yellow operator level
indicator will come on.
Note: If the system goes out of operator mode after 5 minutes, you
must re-enter the operator code +
5
Silence alarm by pressing
The red FIRE indicator and
zone indicator(s) light up with
steady light.
Control outputs remain active.
Note: If necessary, the sounders can be re-activated by once again
operating .
When the fire is extinguished and all necessary repair work is
implemented (smoke is exhausted, new glass replaced in the
manual call-points, etc.), the system should be returned to
normal operating mode.
6
Reset the system by pressing
The red FIRE indicator and
zone indicator(s) go out.
Note: If a detector zone remains in alarm status after resetting the
system, the alarm will be activated again. In such an instance
the above steps must be repeated.
One or more detectors/manual call-points send an alarm signal from a detector zone.
The red FIRE indicator light flashes.
Red flashing zone lights
indicate the activated
detector zone(s).
Internal buzzer is activated.
All alarm units linked to the panel are activated (1 sec.
ON , 1 sec. OFF)
*Continuous alarm si