EasyManua.ls Logo

Autronica BX-10 - Fault;Disabling;Testing - Alarm Outputs; Error;Disabling;Testing - General Alarm Output (BMA); Error;Disabling;Testing - General Fault Output (BMF); Immediate Warning Disabled

Autronica BX-10
39 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
Operators Handbook, Fire Alarm Control panel BX-10, P-BX10/FE - Rev.F, 030123, Autronica Fire and Security AS
Page 28
10.1.4 Fault/disabling/testing - alarm outputs
Fault/Disabling/Test
Yellow indicator with 3 functions: fault, disabling or testing of alarm outputs.
Error status
Disabling status
Test mode
Activated by break or short-
circuit in alarm outputs
(AK1 and AK2) FAD's.
Flashing yellow light
with fault – remains
active until the control
panel is reset.
Disabling indication has
priority over error or test.
Constant yellow light as
long as alarm output is
disabled.
Not implemented
10.1.5 Error/disabling/testing - general alarm output (BMA)
Fault/Disabling/Test
Yellow indicator with 3 functions: fault, disabling or testing of alarm transfer.
Error status
Disabling status
Test mode
Monitoring of errors/faults
in general alarm outputs.
Activated by break or
short circuit in BMA or
fuse F3.
Flashing yellow light –
remains active until the
control panel is reset.
Disabling function is activated
in operator mode by pressing
key 7.
Constant yellow light as
long as the outputs are
disabled.
Not implemented
10.1.6 Error/disabling/testing - general fault output (BMF)
Fault/Disabling/Test
Yellow indicator with 3 functions: fault, disabling or testing of alarm transfer.
Error status
Disabling status
Test mode
Monitoring of errors/faults
in general fault outputs.
Activated by break or
short circuit in BMF.
Flashing yellow light –
remains active until the
control panel is reset.
Disabling function is activated
in operator mode by pressing
key 8.
Constant yellow light as
long as the outputs are
disabled.
Not implemented
10.1.7 Immediate warning disabled
Fault/Disabling/Test
Immediate warning disabled
Yellow indicator is activated when the panel is configured for delayed alarm on the
alarm outputs (AK) and common alarm output (BMA) (appendix 10.2).
Constant yellow light is activated by configuration of a delayed alarm via operator
code and key-code, or via an auxiliary switch.
10.1.8 Fault in battery or battery fuse (F9)
Fault
Battery
Yellow indicator is activated if a fault occurs. Activated if the control panel registers an
operating voltage below 22.5V or above 30.0V
Flashing yellow light with fault– remains until control panel is reset.

Related product manuals