Appendix
Operators Handbook, Fire Alarm Control panel BX-10, P-BX10/FE - Rev.F, 030123, Autronica Fire and Security AS
Page 30
10.2 BX-10 Control Panel variants
BX-10 can now be supplied with variants of the system program
adapted to particular markets and special functions, e.g. the agricultural
industry, maritime installations, and control panels to which intruder
detectors can be connected.
Special program versions for specific countries are also available. If the
program features for the individual country do not vary in relation to
the Norwegian version, then only the front panel notation (language) is
different.
The following versions are available:
BX-10 Standard version, Norwegian.
BX-10L Agricultural version, Norwegian.
BX-10I Fire and intruder version, Norwegian.
BX-10LI Agricultural version with fire and intruder
detection, Norwegian.
BX-10M Maritime version.
BX-10M2 Maritime special version
BX-10m/xx-24 Maritime, 24V DC powered
BX-10M2/xx-24 Maritime special version, 24V DC powered
BX-10/S1 Swedish version.
BX-10I/S1 Swedish version with fire and intruder detection
BX-10/NL Dutch version
Language variants of standard versions are denoted by BX-10M/xx,
where xx is the language code.
Brief explanation of what is unique about the different control panel
variants.
BX-10: Standard Norwegian version (program P1BX10-110-xx)
This version has an automatic safety coupling for disabled
functions after 12 and 24 hours. This means that:
• disabled detector zones (loops) are automatically
restored after 24 hours (oversight safety coupling).
This automatic coupling overrides any disabling via an
external trip switch with a closed contact.
• disabling of immediate detection (D/N function) is
automatically restored after 12 hours.
BX-10L: Agricultural version (P1BX10-112-xx)
This version has a 4-hour automatic safety coupling feature
for disabled loops. Otherwise it is identical to the standard
version.
BX-10I: Fire and intruder detection (P1BX10-113-xx).
This version does not
have automatic safety coupling for
loop 4. This enables intruder detectors on loop 4 to be
disabled with the possibility for manual disabling/restoring
via an external code switch on input 4.