Appendix
Operators Handbook, Fire Alarm Control panel BX-10, P-BX10/FE - Rev.F, 030123, Autronica Fire and Security AS
Page 31
BX-10LI: Agricultural version with fire and intruder detection
(P1BX10-113-xx).
Combination of functions for BX-10L and BX-10I versions.
BX-10M: Maritime version (P1BX10-116-xx).
This version is approved in accordance with the maritime
regulations, SOLAS. The maritime version has the
following variances from the standard version:
• Internal buzzer and alarm sounders (AK1 and AK2) are
activated with a fixed signal on alarm.
• The delay for the alarm outputs is 2 minutes. The BMA
output has no delay.
• A stropping between terminator 60 and 64 activates the
standard 2 minutes delay of alarm outputs.
• No LED indication on front panel for delayed alarm
outputs.
• No automatically restoring of delayed alarm function
after 12 hours.
• Sounder alarm output signal, 7 short and 1 long, by
strapping between connection 5 and 6.
BX-10M2: Maritime special version (P1BX10-118-xx)
Same basic functions as the standard M-version, except for
the following functions:
• 5 minutes delay of main power supply default
• Pulsating sounder outputs (1s ON, 1 s OFF)
• No activation of 7 short and 1 long signal by strapping
5 and 6
BX-10M/xx-24: Maritime version, 24 V DC powered (P1BX10-116-
xx)
• 24 V DC powered panel (18-32 V DC)
• No room for battery inside cabinet
• Standard maritime functions like BX-10
BX-10M2: Maritime special version, 24 V DC powered (P1BX10-118-
xx)
• Functions like BX-10M2
• 24 V DC powered (18-32 V DC)
• No room for battery inside cabinet
BX-10/S1: Swedish version (P1BX10-114-xx)
Same as the standard Norwegian version, but with the
possibility for connection of an external key box for a
standard fire key. This is made possible by the external key
switch giving 0 volts on input 5 on the terminal board. The
key function will work parallel with operator code 110.