Operating the control panel
Operators Handbook, Fire Alarm Control panel BX-10, P-BX10/FE - Rev.F, 030123, Autronica Fire and Security AS
Page 5
2. Operating the control panel
2.1 Operating levels
The BX-10 fire alarm control panel has 2 operating levels. Level 1 is
the lowest level of access and does not require a password.
The following functions are accessible within the respective operating
level:
Level Accessible functions
1
No password protection. Normal mode.
resetting of internal audio warning device (with alarms and faults).
testing of indicator lamps/internal audio warning device.
2
Operator code is required. Yellow OPERATOR LEVEL light comes on
indicating that the system is in operator mode.
cancelling/reactivating of the alarm outputs
resetting of the control panel from alarm or error status
disabling of functions (zones 1-4, alarm outputs, control outputs)
disabling of immediate warning (D/N function)
The operator code for operating level 2 shall include a minimum of 3
digits.
For relevant operator codes, see sub-section. 2.4.3.
IMPORTANT:
All operator code entries are confirmed by pressing this key -
2.2 Operator mode/service mode operations
Keying the operator code + enables the operator to access the
system in operator mode The system will remain in this mode for a
predetermined time (time (the default is 5 minutes after the last key-
stroke), after which it will automatically return to normal mode unless
the operator or service code is entered one more time.
Operator code: 110 +