OPS-LINE (DS1 Off-Premises Station Line)
Issue 1 May 2002
8-857555-233-142
Error Log Entries and Test to Clear Values
Notes:
a. This is a software audit error that does not indicate any hardware
malfunction. Run the short test sequence, and investigate associated
errors (if any).
b. The DS1 OPS Line has been busied out by a busyout station <ext>
command. No calls can be made on this line.
c. This error type indicates that the circuit pack has been removed or has
been insane for more than 11 minutes. To clear the error, reinsert or
replace the circuit pack.
d. Error Type 1793 indicates a problem with the DS1 Interface circuit pack.
Since there is no error against the OPS-LINE port, no alarm is raised
against the OPS-LINE port. However, there should be errors logged
against the DS1 Interface circuit pack. Look for DS1-BD/UDS1-BD errors
in the Hardware Error Log, and follow the appropriate procedures provided
in the ‘‘DS1-BD (DS1 Interface Circuit Pack)’’ on page 8-456.
Table 8-364. DS1 OPS Maintenance Error Log Entries
Error
Type
Aux
Data Associated Test
Alarm
Level
On/Off
Board Test to Clear Value
0
1
1. Run the short test sequence first. If every test passes, run the long test sequence. Refer to each appropriate
test’s description, and follow its recommended procedures.
0 Any Any Any test station <ext>
15(a) Any Audit and Update test
(#36)
18(b) 0 busyout station <ext> WARNING OFF release station <ext>
130(c) None WARNING ON test station <ext>
1281 Conference Circuit test
(#7)
MINOR ON test station <ext> l r 4
1537 NPE Crosstalk test (#6) MINOR ON test station <ext> l r 3
1793(d) test board UUCSS l