RALM-SVC (Remote Alarm Service)
Issue 1 May 2002
8-983555-233-142
RALM-SVC (Remote Alarm Service)
For the RALM-SVC MO, maintenance software does special periodic testing
every 60 seconds. These tests verify that the standby servers components are
operating correctly.
Alarm Log Entries
Notes:
a. Event ID #1
SME_ARB test failed This periodic test verifies the Arbiters
Remote Alarm Service functionality. The test queries the standby server to
find out whether it can generate alarms. (Both servers must have their own
alarm-generation utilities.) If the test fails three consecutive times, the
following Super alarm is logged:
#1,ACT,SME,A,1,MIN,Far-end alarm service is down
b. Event ID #2
Standby_PN_Check test failed This periodic test:
1. Queries the standby server about the state of health of its EPNs
2. Compares the acquired information to an administered value
A failure indicates that a mismatch occurred and that the standby server is
out of sync. If this test fails 2 consecutive times, the following Major alarm
is logged:
#1,ACT,SME,A,2,MAJ,Standby Port-Network check failed
System Technician-Demanded Tests: Descriptions
and Error Codes
This MO provides no on-demand tests for system technicians.
MOs Name (in
Alarm Log)
Alarm
Level Initial Command to Run Full Name of MO
RALM-SVC SUPER None Remote Alarm Service
RALM-SVC MAJOR None Remote Alarm Service
Table 8-416. RALM SVC Alarm Log Entries
EVENT
ID#
Aux
Data Associated Test
Alarm
Level
On/Off
Board Test to Clear Value
1 (a) SME_ARB test SUPER ON testdupboard
2 (b) Standby_PN Check test MAJOR ON testdupboard
Continued on next page