MAPD-BD (MAPD Interface Circuit Pack TN802)
Issue 1 May 2002 8-713555-233-142
8
MAPD-BD (MAPD Interface Circuit
Pack TN802)
The TN802 Multiple Application Platform for DEFINITY (MAP-D) circuit pack
allows sending voice and fax from S8700 IP Connect through the Internet to
another S8700 IP Connect also having this feature or to other PBXs that are
equipped with the Internet Telephony server (ITS-E).
Throughout this section the term TN802 means the MAP-D IP trunk circuit pack.
Be sure to observe these special considerations for the TN802:
■ Port alarms on this circuit pack display as “TIE-DS1” in the Alarm and Error
logs.
■ The reset board command reboots the MAPD PC CPU, but busyout
board only busies out every emulated port on the board.
■ Switch resets that take the switch out of service for more than 20 seconds
also cause the MAPD's PC to reboot, which takes several minutes to
complete.
Switch-Demanded Tests
Switch-demanded diagnostic tests on the TN802 do not run unless the Internet
trunking application is running on Windows NT™, located on the circuit pack.
MO’s Name
(in Alarm Log)
Alarm
Level Initial Command to Run
1
1. UU is the universal cabinet number (1–64). C is the carrier designation (A, B, C, or D). SS is the number of the
slot where the circuit pack resides (01–10).
Full Name of MO
MAPD-BD MAJOR test board UUCSS sh MAPD Interface circuit pack
MAPD-BD MINOR test board UUCSS l MAPD Interface circuit pack
MAPD-BD WARNING test board UUCSS sh MAPD Interface circuit pack