Maintenance Object Repair Procedure
555-233-142
8-730 Issue 1 May 2002
Completely remove the MAPD-BD from the system:
a. Shut down NT (see ‘‘Shutting Down NT on the TN802’’)
b. Remove any administered DS1 trunks, access endpoints, or
PRI endpoints associated with the circuit pack from their
respective trunk groups.
c. Remove the DS1 (remove ds1 UUCSS) and circuit pack
(change circuit pack UUCSS) administration.
If the circuit pack is properly administered and the red LED is still on, follow
the instructions for LED Alarms with Error Type 1 in Chapter 7.
b. Error Type 2NT is down and the system attempts to reset the board. If
the reset fails, the board is probably bad.
1. Replace the circuit pack.
c. Error Type 18The circuit pack has been busied out.
1. Release the board (release board UUCSS).
d. Error Type 23 and 1025: The MAPD-BD circuit pack is not completely
administered. In addition to insertion, the MAPD circuit pack must have all
of the following administration:
Have an entry in the circuit plan (change circuit pack)
Be administered as DS1 (add ds1 UUCSS)
The MAPD circuit pack differs from others in that inserting it into the switch
backplane is not enough to make the board usable.
e. Error Type 125, no Aux Data:A wrong circuit pack is inserted in the slot
where this circuit pack is logically administered. To resolve this problem,
either:
1. Remove the wrong circuit pack and insert the logically administered
circuit pack
or
Re-administer this slot (change circuit-pack) to match the circuit
pack inserted.
f. Error Type 257This error is associated with the Common Port circuit
pack maintenance test. See ‘‘XXX-BD (Common Port Circuit Pack)’’ on
page 8-1374 for details.