Maintenance Object Repair Procedure
555-233-142
8-744 Issue 1 May 2002
Error Log Entries and Test to Clear Values
Table 8-314. DS1 Interface Circuit Pack Maintenance Error Log Entries
Error
Type
Aux
Data Associated Test Alarm Level
On/Off
Board Test to Clear Value
0
1
1. Run the short test sequence first. If every test passes, run the long test sequence. Refer to each appropriate
test’s description, and follow its recommended procedures.
0 Any Any Any test board UUCSS
1(a) 0 Circuit pack removed or
SAKI test (#53)
MINOR
WARNING
2
2. If ports are assigned to the circuit pack, then a minor alarm is raised. If no ports are assigned to the circuit pack,
then a warning alarm is raised. The alarm is raised after the circuit pack has been missing for a period of 15
minutes. Warning alarms are also raised against any ports administered on the circuit pack.
ON
18(b) 0 busyout board UUCSS WARNING OFF release board UUCSS
23(c) 0 WARNING OFF add ds1 UUCSS
125(d) None None MINOR
WARNING
3
3. Minor alarms on this MO may be downgraded to warning alarms based on values set in the set options
command.
ON
257(e) 6553
5
Control Channel Loop
test (#52)
MINOR ON test board UUCSS l r 2
1538(f) Any Hyper activity MINOR
WARNING
3
ON
1793 Any NIC Loss Of Signal MINOR
WARNING
3
test board UUCSS l r 2
2049(g) Any NT PC Failure MINOR
WARNING
3
reset board UUCSS
2305 Any IP Address Inconsistency test board UUCSS l r 2
2561 Any Ping Error MINOR
WARNING
3
test board UUCSS l r 5
3841(h) 4358 Log Only
3999(i) Any None
Continued on next page