UDS1-BD (UDS1 Interface Circuit Pack)
Issue 1 May 2002
8-1269555-233-142
FAIL Minor alarms are often accompanied by slip and misframe alarms against the
board. Trunk alarms and hardware error logs may occur on the associated
trunks.
If the UDS1 connects to a T1 network facility or to another switch, do the
following:
1. The performance of the DS1 link between the UDS1 interface circuit pack
and the remote DS1 endpoint is poor. Enter the list measurement
ds1-log UUCSS command to read the error seconds measurement.
2. Verify that both endpoints of the DS1 link are administered using the same
signaling mode, framing mode, and line coding.
3. Contact T1 Network Service or the technician at the remote switch to
diagnose the equipment.
4. Check the physical connectivity of the UDS1 interface circuit packs and the
cable.
5. Replace the local UDS1 interface circuit pack, and repeat the test.
FAIL
(contd.)
If the UDS1 connects to a line-side terminating device (for example, a PRI
terminal adapter), do the following:
1. The performance of the DS1 link between the UDS1 interface circuit pack
and the line-side terminating device is very poor. Enter the list
measurement ds1-log UUCSS command to read the error seconds
measurement.
2. Verify that the switch DS1 and the line-side terminating device are
administered using the same signaling mode, framing mode, and line
coding.
3. Investigate the maintenance status of the line-side terminating device.
Obtain the error seconds measurement on the terminating device (if
possible). Refer to the Line-Side Terminating Device Operating Manual
for information.
4. Contact the vendor of the line-side terminating device to diagnose the
equipment.
5. Check the physical connection of the UDS1 interface circuit pack to the
terminating device, and check the premise distribution system (or the
intra-premise wiring) for physical connection failures.
6. Replace the local UDS1 interface circuit pack and repeat the test.
Table 8-531. Test #143 Minor Alarm Inquiry Test Continued
Error
Code
Tes t
Result Description / Recommendation
Continued on next page